Home » IEC 62443 Explained: A Practical Guide for Machine Builders

IEC 62443 Explained: A Practical Guide for Machine Builders

6 views
Industrial control devices connected to a security shield, IEC 62443 guide for machine builders

IEC 62443 is the international series of standards for the security of industrial automation and control systems (IACS). If you build machines that connect to a network, you will meet it sooner or later. Customers already ask for it in tenders. In addition, new EU rules push manufacturers toward the same practices.

What IEC 62443 covers

The series addresses IACS security across the whole lifecycle. The IEC and the ISA99 committee develop it together. In the United States, ISA publishes the same content as ANSI/ISA 62443. For a first overview, the IEC background page on IEC 62443 is a good starting point.

The documents sit in four tiers:

  • General: concepts, terms and models used throughout the series.
  • Policies and procedures: security programs for asset owners, requirements for service providers and patch management.
  • System: risk assessment, system design and system security requirements.
  • Component: secure product development and technical requirements for components.

Three roles, and where machine builders fit

The standard defines three main roles: the asset owner, the system integrator and the product supplier. Machine builders often play two of them at once. When you design a control cabinet or an HMI package, you act as a product supplier. When you deliver and commission a complete line, you act as a system integrator. Therefore, you need to know which parts of the series apply to each project.

The parts that matter most to you

  • IEC 62443-4-1: requirements for a secure product development lifecycle.
  • IEC 62443-4-2: technical security requirements for components such as embedded devices, network components and software applications.
  • IEC 62443-3-2: security risk assessment and system design, including zones and conduits.
  • IEC 62443-3-3: system security requirements and security levels.
  • IEC 62443-2-4: requirements for service providers during integration and maintenance.

Foundational requirements and security levels

The standard groups its technical requirements into seven foundational requirements:

  1. Identification and authentication control
  2. Use control
  3. System integrity
  4. Data confidentiality
  5. Restricted data flow
  6. Timely response to events
  7. Resource availability

You can meet each requirement at a security level from SL 1 to SL 4. A higher level protects against a more capable attacker. SL 1 covers casual or accidental violations. SL 4 covers attackers with extended resources and strong motivation. Most projects set a target level per zone. As a result, you do not need the highest level everywhere.

Six practical first steps

  1. List your products and interfaces. Note every network port, remote access path and service.
  2. Run a risk assessment. Define zones and conduits as described in part 3-2.
  3. Agree a target security level for each zone with your customer.
  4. Check your components. Ask suppliers for their IEC 62443-4-2 documentation.
  5. Adopt secure development habits. Change default passwords, close unused ports and plan how you will deliver patches.
  6. Prepare a vulnerability process. Decide who receives reports and how you answer them.

How it relates to the EU Cyber Resilience Act

The Cyber Resilience Act (CRA) is an EU regulation for products with digital elements. Its reporting obligations have applied since 11 September 2026. The main obligations follow on 11 December 2027. The reporting duty also reaches products that are already on the market. The European Commission explains the timeline.

IEC 62443 and the CRA are not the same thing. The CRA is law, while IEC 62443 is a set of standards. Nevertheless, a secure development lifecycle based on part 4-1 gives you a solid base for CRA work. Compliance with one does not automatically prove compliance with the other, so check with your legal advisor whether your products fall within scope.

Why it matters for machine builders

Customers increasingly treat security as a purchasing criterion. Builders who document their risk assessment and their security levels early answer audits faster. Moreover, the same documents help you meet new legal duties. If you want to see which suppliers offer security-ready networking hardware, read our Weidmüller product news or browse all manufacturers. Virtual controllers also move control onto IT infrastructure, so see our guide to the virtual PLC as well.