The EtherCAT Technology Group (ETG) has released version 1.0 of the ETG.1800 EtherCAT Security Profile. The specification meets the security requirements of IEC 62443-3-3 for Security Level 2 (SL 2). It does so without any change to the EtherCAT technology itself. Users can therefore apply the profile with devices that are already on the market, about one year before the EU Cyber Resilience Act (CRA) becomes fully applicable.
What the EtherCAT Security Profile covers
The profile follows the successful assessment of EtherCAT by UL Solutions in early 2026. It references existing EtherCAT specifications to fulfil the applicable system requirements (SRs) of IEC 62443-3-3. This is the international standard for the cybersecurity of industrial control systems.
Both IEC 62443 and the CRA state that the risk of a plant depends on its application and environment. A risk assessment must therefore define the needed protection. For this reason, the ETG specification describes three typical application scenarios with different threat levels. They also serve as a template for your own risk assessment of a machine or plant.
| Blueprint scenario | Attacker capability | Status of EtherCAT support |
|---|---|---|
| Scenario 1 | SL 2; typical production hall, non-public environment | Covered by ETG.1800 v1.0 with existing EtherCAT functions |
| Scenario 2 | SL 3; higher attacker capability | Compatible extensions in development (MainDevice and configuration tool) |
| Scenario 3 | SL 3 plus data confidentiality | Device authentication and encryption being defined |
Security by architecture, not by add-ons
Security concepts for conventional fieldbus and Industrial Ethernet systems often rely on a “secure zone”. This approach needs physical barriers against unauthorized access. However, such barriers are hard to maintain when fieldbus cables run across a whole machine or plant. Extra security extensions are then necessary. They add configuration effort, reduce cyclic performance and make operation more complex.
EtherCAT takes a different route. It relies on a secure system architecture instead of additional IT security measures. The frames are processed in hardware, without a conventional software stack. This operating principle gives the technology a solid base for cybersecurity robustness.
25 existing functions fulfil scenario 1
The specification uses a total of 25 EtherCAT system functions to meet the IEC 62443-3-3 requirements of scenario 1. All of them already exist in the current EtherCAT technology. Consequently, the protocol stays unchanged. Many installations that match scenario 1 may already comply, although some configuration settings might need adjustment.
Roadmap for scenarios 2 and 3
For scenario 2, the ETG is developing compatible extensions. They add software functions to the MainDevice and the configuration tool. The SubDevices need no changes. For scenario 3, the group is defining device authentication and data encryption. These functions need software support in both the MainDevice and the SubDevices. Nevertheless, the EtherCAT SubDevice Controllers need no hardware changes. The ETG will add these measures to its specifications in stages.
Why it matters for engineers
Machine builders and integrators can start now. First, run a risk assessment of your machine or plant using the three scenarios. Next, map it to the profile and check the device configuration. Finally, document the result as input for CRA conformity work. Dr. Guido Beckmann, Chair of the ETG Technical Committee, expects that a large share of installations map to scenario 1. In his view, they will fulfil the requirements with no changes or with simple configuration adjustments.
For more detail, see the EtherCAT Technology Group website and the European Commission page on the Cyber Resilience Act. More news from the group is in our EtherCAT Technology Group section. Related news: Agibot joins the EtherCAT Technology Group as member 9,000. Browse more industrial communications news as well.